This specification covers machine made solid uncored carbon brick produced from either metallurgical or petroleum calcined coke, baked, and suitable for use in masonry construction.
This material is normally used with carbon filled chemical-resistant mortars.
The carbon brick shall exhibit chemical resistance to the following chemical media:
It shall also comply with the specified values for compressive strength, modulus of rupture, water absorption, and maximum ash content.
1.1 This specification covers machine made solid uncored carbon brick produced from either metallurgical or petroleum calcined coke, baked to a minimum 1850Β°F (1010Β°C), and suitable for use in masonry construction which will be exposed to various chemicals.
These units are designed primarily for industries using hydrofluoric acid, fluoride salts, and high concentrations of alkalies such as sodium and potassium hydroxide. Carbon brick are normally used with carbon filled chemical-resistant mortars.
TABLE 1 General Guide to Chemical Resistance of Carbon Brick
Note 1βThis table is intended for use as a general guide to the resistance of carbon brick in immersion service at ambient temperatures. Specific recommendations should be obtained from the carbon brick manufacturer. Carbon brick can be used to 650Β°F (340Β°C). Over 650Β°F (340Β°C), strict environmental control is paramount to ensure that the environment is non-oxidizing.
| Medium | Chemical ResistanceA |
|---|---|
| Nitric Acid, to 40β% | R |
| Hydrofluoric Acid, to 40β% | R |
| Blendβ25β% Nitric, 10β% Hydrofluoric, 65β% Water | R |
| Hydrochloric Acid, to 35β% | R |
| Phosphoric Acid, to 75β% | R |
| Sulfuric Acid, to 50β% | R |
| Sodium Hydroxide, to 50β% | R |
| Potassium Hydroxide, to 50β% | R |
A R = Recommended.
TABLE 2 Physical and Chemical Requirements
| Property | Value |
|---|---|
| Compressive Strength, psi (MPa), min | 6000 (41) |
| Modulus of Rupture, psi (MPa), min | 1500 (10) |
| Water Absorption, %, max | 10 |
| Ash, %, max | 8 |
1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.3 This standard does not purport to address the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.