Electromagnetic compatibility (EMC) -- Environment. Compatibility levels in power distribution systems in industrial locations for low-frequency conducted disturbances
IEC 61000-2-4:2024 RLV is available which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.
IEC 61000-2-4:2024 is related to conducted disturbances in the frequency range from 0 kHz to 150 kHz. It gives compatibility levels in differential mode (L-L and L-N) for industrial locations, with a nominal voltage up to 35 kV and a nominal frequency of 50 Hz or 60 Hz.
NOTE 1 Industrial locations are defined in 3.1.8. Power distribution systems on ships, aircraft, offshore platforms and railways are not included.
NOTE 2 See also Annex E. The compatibility levels specified in this document apply at the in-plant point of coupling (IPC). The level of the low-frequency disturbances at the terminals of equipment receiving its supply from the IPC is generally assumed to be similar to the disturbance level at the IPC itself. However, in some situations this is not the case, particularly when a long feeder is dedicated to the supply of a particular load, or when a disturbance is generated or amplified within the installation of which the equipment forms a part.
Compatibility levels are specified for the types of low-frequency electromagnetic disturbances expected at any in-plant point of coupling (IPC) within industrial locations, for guidance in the definition of:
The disturbance phenomena considered are:
The compatibility levels are given for different classes of environment determined by the characteristics of the supply network and loads.
NOTE 4 Compatibility levels at the point of common coupling (PCC) on public networks are specified in IEC 61000‑2‑2 for low-voltage networks and IEC 61000‑2‑12 for medium-voltage networks. IEC TR 61000‑3‑6 and IEC TR 61000‑3‑7 describe the approach of power distribution system operators to the limitation of emissions from installations and large loads.
This third edition cancels and replaces the second edition published in 2002. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition: