IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems
New IEEE Standard - Inactive-Withdrawn.
Practical instrumentation methods are presented for measuring the ac characteristics of large, extended or interconnected grounding systems.
Measurements of impedance to remote earth, step and touch potentials, and current distributions are covered for grounding systems ranging in complexity from small grids (less than 900m2), with only a few connected overhead or direct burial bare concentric (2) neutrals, to large grids (greater than 20,000m2), with many connected neutrals, overhead ground wires (sky wires), counterpoises, grid tie conductors, cable shields, and metallic pipes.
This standard addresses:
Test methods and instrumentation techniques used to measure the ac characteristics of large grounding systems include the following topics:
Grounding electrodes consisting of a single ground rod, arrays of ground rods, tower footings, and many grids (if no external grounding is connected) can be measured, interference voltages permitting, with methods outlined in IEEE Std 81-1983 [2].
Even if a large grid has an impedance phase angle of 18°, the resistance component will be only 5% lower than its impedance.
However, for large grounding grids in low-resistive earth (<75 Ω-m) and for grounding systems that have numerous extended grounding conductors, the impedance could be significantly greater than the resistive component measured with the conventional test sets of IEEE Std 81-1983.
The purpose of this guide is to present practical instrumentation methods that may be used for the measurement of impedance to remote earth, step and touch potentials, and current distributions of large extended or interconnected grounding systems ranging in complexity from small grids (less than 900 m2), with only a few connected overhead or direct burial bare concentric neutrals, to large grids (greater than 20,000 m2), with many connected neutrals, overhead ground wires (sky wires), counterpoises, grid tie conductors, cable shields, and metallic pipes.